top of page

When you feel that power generation from a solar PV system is "low," the causes can vary widely: dirty panels, shading, equipment faults, weather, wiring, misconfiguration, and so on. However, what you should check first in practice is whether the power generation monitoring settings are functioning correctly before going to the site. Power generation monitoring is not a device that physically prevents a drop in generation, but it is an important mechanism for detecting signs of decline early, prioritizing inspections, and reducing delays in response. If the monitoring thresholds and alert conditions do not match actual site conditions, it can become difficult to notice anomalies, or conversely, unnecessary notifications may be so frequent that you overlook changes you should actually be watching. In this article, aimed at operations personnel searching for "low power generation," we organize and explain five power generation monitoring settings you should review to reduce missed detections of generation declines.


Table of Contents

Basic perspectives to avoid overlooking low power output

Revision 1: Adjust the reference value for power generation to match site conditions

Review 2 Adjust alert thresholds and notification conditions

Review 3: Configure comparison settings for solar radiation and weather conditions

Review 4: Reassess monitoring granularity per string and per equipment

Revision 5: Strengthen detection settings for data loss and communication anomalies

Summary for implementing operations to prevent power output decline


Basic perspectives to avoid overlooking low power output

When determining that power output is low, simply looking at the output for that day alone makes it difficult to isolate the cause. Solar power generation is influenced by multiple factors such as weather, season, temperature, solar irradiance, snowfall, surrounding shadows, system capacity, installation angle, and the operating status of the power conditioner. A decrease in output on cloudy or rainy days is a natural fluctuation and is not necessarily an equipment fault. On the other hand, changes such as only part of the same system showing low output while sunny weather continues, a larger drop compared to the same month of the previous year, or a sudden decline only during a specific time period can be signs that warrant inspection.


The purpose of reviewing power generation monitoring settings is not to alert on every decline in output. The important thing is to move closer to a state where normal fluctuations can be distinguished from changes that require inspection. In practice, monitoring settings that produce too many notifications tend not to be used. If even small fluctuations trigger daily notifications, staff can become desensitized to alerts and may miss genuinely significant drops. Conversely, if thresholds are too lax, a low generation state may not be noticed until it is obvious, lengthening the period of lost production.


When checking for a drop in power generation, it's important not only to look at the generation figures themselves but also to consider how you set the comparison baseline. Depending on whether you compare to the previous day, the same month in the previous year, nearby facilities or another system within the same plant, or examine generation relative to solar irradiance, anomalies will appear differently. With appropriately configured generation monitoring, you can to some extent sort out before on-site inspection whether it's "an overall decrease," "a decrease in part of the equipment," or "a communication or measurement issue."


Before rushing to take on-site action when power generation is low, it is important to first check whether the monitoring settings have become outdated. If there have been equipment additions, panel replacements, equipment upgrades, vegetation growth, changes in surrounding buildings, or changes to inspection rules, previous monitoring settings may no longer match the current situation. Because the environment around power generation facilities continues to change after installation, monitoring settings are not a one-time decision but a management item that should be reviewed periodically.


Revision 1: Adjust the baseline power generation value to match site conditions

The first thing to review is the baseline used to determine a decrease in power generation. If the baseline does not match site conditions, it becomes difficult to correctly judge when generation is low. For example, if a simple assumed value based only on installed capacity is used, actual solar irradiance conditions, installation tilt, azimuth, nearby shading, and regional weather trends may not be adequately reflected. As a result, normal-range variations may be judged as anomalies, or conversely, genuine declines that should be inspected may be overlooked.


When reviewing baseline values, it is effective to use historical performance data in addition to the equipment's rated capacity. Checking how much power was generated in the same season, the same month, and under similar weather conditions makes it easier to create standards that reflect the actual conditions at each site. Especially for systems that seem to have low power output, do not judge based only on the most recent few days; it is important to look at trends over several weeks to months. Declines due to short-term weather variations and declines due to gradual degradation or soiling appear differently on graphs.


When setting reference values, it is also important to decide whether to view them on a daily, monthly, or time-of-day basis. If you only look at daily generation, you can miss changes such as output being low only in the morning, only in the afternoon, or being limited around noon. For example, if shadows from nearby trees or buildings occur during specific times of day, they may not appear as a major anomaly in the day’s total but can be confirmed as a drop when viewed by time period. If your monitoring settings allow time-of-day comparisons, preparing not only daily totals but also time-of-day reference values makes it easier to infer the cause.


It is also necessary to review threshold values for each season. In summer, even with longer sunshine hours, high temperatures can suppress output growth, and in winter, favorable temperature conditions can still be affected by sunshine hours, snowfall, and frost. Monitoring with the same thresholds year‑round can cause alerts to be skewed by season. In practice, it is important to choose a method suited to the site’s management framework, such as roughly adjusting thresholds by spring, summer, autumn, and winter, using expected values for each month, or comparing with historical results from the same month.


If the threshold is set too high, normal weather variations will frequently trigger low-output judgments. Conversely, if it is set too low, you won’t receive notifications even if generation remains low for an extended period. The threshold should be based not on the “ideal maximum generation” but on the “range that can be expected during normal site operation.” Be careful not to include data from clearly faulty periods or communication outages in the historical baseline, as that will make the threshold too low. Using data from periods that have been inspected and determined to be normal as the baseline results in monitoring settings that are more practical for operational use.


Review 2: Adjust alert thresholds and notification conditions

To detect declines in power output quickly, reviewing alert thresholds is essential. Alerts are a useful feature, but coarse settings make them impractical in operation. For example, a setting that notifies every time output drops slightly increases the verification workload for staff. Conversely, a setting that only notifies when output falls dramatically can lead to long periods before a decline is noticed. Alerts for power monitoring should not simply be made stricter; it is important to tune them so they catch the anomalies that require action.


When considering thresholds, you need to look at both the rate of decline and the duration. If power output temporarily drops, it may be caused by passing clouds or short-term weather changes. However, if a decline beyond a certain level continues for several hours, or the output falls below the threshold for multiple consecutive days, the priority for inspection may increase. In alert settings, establishing conditions that detect sustained drops as well as instantaneous dips makes it easier to catch important changes while reducing unnecessary notifications.


It is desirable to design notification conditions to include not only the total power generation of the entire facility but also comparisons to reference systems. For example, if only some of several systems within the same power plant are showing a decline, local soiling, shading, wiring, or equipment problems—rather than weather—are suspected. Even if overall power generation is low, if solar irradiance has fallen significantly, weather-related causes become more likely. If alerts only monitor raw power output, it becomes difficult to distinguish these differences. Where possible, it is practical to include in notification conditions not only the absolute value of power generation but also comparisons with equipment under the same conditions and the ratio of generation to solar irradiance.


Dividing alert severity is also effective. If all notifications are treated the same, minor drops and highly urgent drops become mixed. For example, if you have an advisory level that requires confirmation, a caution level that prompts early consideration of an on-site check, and an emergency level that suggests equipment shutdown or a substantial drop—so that response priorities are clear—responsible personnel can act more easily. It is important that notifications convey not only that power generation is low, but also “how low it is,” “how long it has continued,” and “over what area it is occurring.”


Notification recipient settings should also be reviewed. If notifications of decreased power output are not reaching the person responsible, contact details for retired or reassigned personnel remain, or notification rules for nights and holidays are unclear, the monitoring system will not translate into effective operations. Especially when managing multiple sites, it is necessary to clarify who should be notified—on-site staff, maintenance personnel, or management. If notifications are too frequent, rather than sending everything to everyone, it is better to separate recipients according to importance and equipment category.


Furthermore, the verification procedures to follow after an alert is triggered should be reviewed together with the settings. If it isn’t clear whether the staff receiving the notification should first check a specific screen, compare it with solar irradiance, review historical data, or inspect site photos and maintenance records, responses will be inconsistent. An alert doesn’t end with its occurrence; it only has meaning when it leads to the next decision. If you aim to reduce missed drops in power generation, it is important to configure notification conditions and verification procedures as a set.


Review 3 Adjust comparison settings for solar radiation and weather conditions

When considering the causes of low power generation, comparing it with solar irradiance and weather conditions is extremely important. Because photovoltaic power generation is strongly affected by solar irradiance, looking only at the power output and judging it to be low makes it difficult to determine whether the issue lies with the equipment or the weather. It is natural for generation to drop on cloudy or rainy days, but if there is sufficient solar irradiance yet the output does not increase, the cause may be equipment or operational issues. Therefore, in power generation monitoring, it is important to configure the system so that power output and solar irradiance can be checked side by side.


When using solar irradiance data, you need to check whether the measurement location and the actual conditions of the facility are significantly misaligned. The accuracy of comparisons varies depending on whether the data come from a pyranometer installed near the power plant, regional meteorological data, or wide-area estimated data. In areas prone to localized cloud influence, weather data from a point a short distance away may not match the actual power generation. Do not immediately conclude that there is an equipment fault simply because there is a large difference between irradiance and generation; it is important to also confirm the data acquisition conditions.


Don't overlook the effect of ambient temperature. Solar power systems tend to generate more electricity when solar irradiance is strong, but if panel temperatures rise the output can become harder to increase. For that reason, on clear summer days power generation may not rise as much as expected. When you feel the output is low, being able to check not only the irradiance but also the outside air temperature and the environment around the installation will improve the accuracy of your assessment. In particular, if generation differs by season under the same irradiance conditions, you need to consider the influence of temperature.


Snow, frost, yellow sand, dust, fallen leaves, bird droppings, and similar factors also affect the relationship between solar irradiance and power output. If irradiance is sufficient but power output is low, shading or soiling on the panel surface may be the cause. Configuring monitoring so site photos, inspection records, and cleaning records can be reviewed together with power generation data makes it easier to infer the cause of a decline. To reduce missed detections of power output drops, you need a system that can check the site conditions behind the numbers, not just monitor the figures.


Also, by looking at the ratio of power generation to solar irradiance, it becomes easier to distinguish declines caused by weather from declines on the equipment side. For example, if solar irradiance has fallen significantly and power generation has declined in the same way, it is likely due to weather factors. However, if solar irradiance is sufficient but only power generation has dropped significantly, some form of inspection is necessary. If you set up your system to perform this kind of comparison routinely, you can avoid ending with “it was low because it was cloudy today” and detect possible equipment abnormalities earlier.


When comparing with meteorological conditions, the display units of the graphs are also important. Being able to overlay power generation and solar irradiance by time of day, rather than just daily totals, makes it easier to find phenomena that are declining only during specific periods. If it is low only in the morning, clues include shadows on the east side or problems with some equipment; if it is low only in the afternoon, clues include shadows on the west side or the effects of rising temperature. Of course, this alone cannot determine the cause, but it provides material for prioritizing on-site inspections.


Review 4: Reassess monitoring granularity by string and by equipment

To detect drops in power generation early, the granularity of monitoring is important. If you only look at the total generation for the entire plant, low output in some strings or in certain equipment can be masked by the overall figure and hard to notice. Especially in large-scale facilities, abnormalities may be progressing in some parts even if the overall generation hasn’t fallen significantly. In power monitoring settings, it is important to configure monitoring so that, in addition to overall monitoring, you can check by string, by power conditioner, by system, and by area wherever possible.


String-level monitoring is effective for narrowing down the causes of low power output. When you compare strings under similar conditions within the same plant, you may find changes such as only one string being low, only a specific row being low, or differences appearing only during certain time periods. These can point to issues such as soiling, shading, wiring problems, poor connections, equipment outages, or partial panel malfunctions. However, if the installation orientation or shading exposure differs between strings, you should avoid declaring an anomaly based solely on a simple comparison. You must confirm that the comparison conditions are aligned before configuring monitoring settings.


With equipment-specific monitoring, it is important to be able to check the power generation and operating status of each power conditioner. When generation is low, the direction of response changes depending on whether the overall output has dropped evenly or only a single unit's output is low. If only one unit is low, you can prioritize checking the area connected to that device. If multiple units are low at the same time, you should also check solar irradiance, grid-side conditions, output control, and the status of shared equipment. If the monitoring granularity is coarse, this isolation of causes takes longer.


Increasing monitoring granularity tends to improve anomaly detection accuracy, but it also increases the amount of data and number of notifications to manage. Therefore, it is not always best to make everything highly granular. In practice, a staged configuration is easy to use: monitor the entire power plant to detect major drops, use equipment-level monitoring to narrow the scope, and view string-level data as needed. Rather than checking every detail all the time, configuring the system so you can drill down when signs of anomalies appear makes it easier to trace causes while reducing the workload on staff.


It is also important to view the site by area. In a solar power plant, slope, drainage, vegetation, shading, ventilation, and how dirt accumulates can vary by location within the site. If underperforming equipment is concentrated in a particular area, the surrounding environment may be the cause. On the monitoring screen, linking equipment and strings to their on-site positions makes it easier to compare the data with actual site conditions. Presenting information so that you can see where output is declining, rather than just a list of numbers, leads to operations that are less likely to miss drops in generation.


When reviewing the granularity of monitoring, organizing names and management numbers is also essential. Even if a string with low power generation is displayed, response will be delayed if the number does not indicate which location on site it refers to. If drawings, on-site labels, and monitoring screen names do not match, it can lead to verification errors. When reviewing power generation monitoring settings, it is important to check not only thresholds and alerts but also display names, equipment classifications, and the correspondence with on-site locations.


Review 5 Strengthen detection settings for data loss and communication anomalies

When power output is shown as low, it may not be that the system is actually not generating power; rather, the data may not be being collected correctly. Communication failures, measurement device malfunctions, delays in data transmission, mismatched recording intervals, power supply issues, and similar problems can make the power output appear low or even zero. Therefore, in power generation monitoring, it is important not only to have alerts for drops in generation but also to configure detection for data loss and communication anomalies.


If detection of missing data is weak, the cause of an anomaly can be misjudged. For example, when power output suddenly drops to zero, you need to distinguish whether the equipment has stopped or whether communications have merely stopped. If it is a communications failure, on-site equipment may still be generating power. Conversely, if the equipment has actually stopped but is treated as a communications failure, response will be delayed. It is important to configure the system so that power output, equipment status, communication status, and the timestamp of the last data acquisition can be checked together.


The data update interval is also an item that should be reviewed. If the update interval is too long, detection of a decline in power generation may be delayed. Conversely, if the interval is too short and picks up too many minor fluctuations, the burden of notifications and verifications increases. In practice, it is necessary to choose an appropriate update interval according to the scale of the power plant, the management structure, response speed, and required accuracy. For facilities where you want to detect declines in power generation early, it is desirable to confirm that data are updated at a frequency that does not interfere with at least daily checks.


Notification conditions for communication faults are as important as notifications for drops in power generation. It is useful to configure them so causes can be isolated—for example, notify when data has not been updated for a certain period, when data cannot be obtained for several consecutive attempts, and distinguish between cases where only specific equipment is missing and where the entire system is missing. If data from all equipment stops at the same time, problems with the communication line or the aggregator device are suspected. If only some equipment stops, you need to check the affected equipment and the measurement systems around it.


Data gaps also affect monthly reports and evaluations of power generation performance. If you aggregate generated energy while missing periods remain, it may be treated as a lower performance than actual. Before judging that generation is low, it is important to check whether the data to be aggregated are complete and how missing values are being handled. Whether you aggregate missing values as zero, estimate and impute them, or treat them as missing will change the reported results. In practice, deciding in advance how to handle missing data makes it less likely you will have trouble later when identifying causes or providing explanations.


Also, attention must be paid to time drift in measurement instruments. If the timestamps of power generation data, solar irradiance data, weather data, and device status data are misaligned, comparisons for the same time periods will not be accurate. If the recording time for power generation is shifted relative to periods of high irradiance, generation that is actually normal may appear low. When reviewing power monitoring settings, be sure to check data time synchronization, aggregation units, date rollovers, and time zone settings.


Summary to guide operations that prevent declines in power generation

In monitoring configurations designed to prevent drops in power generation, simply displaying power output is insufficient. By aligning five perspectives—baseline values, alert conditions, comparisons with solar irradiance, monitoring granularity, and detection of missing data—you can detect low power output more quickly and more easily proceed to isolate the cause. Because drops in power generation are influenced by weather and site conditions, not all of them can be prevented by monitoring settings alone. However, it is possible to shorten the time to detection, clarify the priority of checks, and reduce delays in response.


First, it is important to have baseline values that reflect the actual conditions on site. Instead of making blanket judgments based solely on installed capacity, you need to understand the range that can be expected during normal operation by taking into account historical performance, season, time of day, and solar irradiance conditions. Next, adjust alert thresholds and notification conditions so you can reduce unnecessary notifications while detecting gradual declines and anomalies in specific equipment. By preparing the notification recipients and response procedures in advance, you make it easier to translate alerts into actual maintenance actions.


Comparisons with solar irradiance and meteorological conditions are also essential. To determine whether low power generation is due to weather or the equipment, you need to look not only at generation but also at irradiance, temperature, snowfall, soiling, and site conditions. In particular, if irradiance is sufficient but generation does not increase, the priority for inspection may rise. Comparing data by time of day makes it easier to find clues to causes such as shading, temperature increases, or localized equipment degradation.


Furthermore, by organizing monitoring granularity by string, by equipment, and by area, you can narrow down the scope of generation declines. Small drops that are not visible in the overall total become easier to detect when comparison targets are made finer. However, if monitoring granularity is made too fine, operational burden increases, so a phased design that progresses from overall monitoring to detailed investigation is practical. If you also organize the mapping between equipment names and field locations, you can reduce rework during on-site inspections.


Finally, you need settings that can detect data loss and communication anomalies. Even if power generation appears low, the data may not have been correctly acquired due to communication or measurement issues. Make it possible to distinguish between a drop in power generation and communication failures, and ensure you can identify the last data acquisition time and any missing periods so you can avoid misjudgments. Analysis of reduced power generation only makes sense with accurate data.


Power generation monitoring is not something you implement and then finish; it is a management platform you cultivate to match changes at the site. Instead of checking only when you feel the output is low, it is important to periodically review the settings and maintain a state that can pick up signs of decline early. If you prepare an environment that links daily monitoring, inspection histories, site photos, and equipment information for integrated review, responses to drops in power generation will be faster and more specific. If you want to reduce missed drops in power generation, it is important to establish a system that treats site management and power generation monitoring as one and to build a structure that enables continuous checking from both numerical data and on-site conditions.


Next Steps:
Explore LRTK Products & Workflows

LRTK helps professionals capture absolute coordinates, create georeferenced point clouds, and streamline surveying and construction workflows. Explore the products below, or contact us for a demo, pricing, or implementation support.

LRTK supercharges field accuracy and efficiency

The LRTK series delivers high-precision GNSS positioning for construction, civil engineering, and surveying, enabling significant reductions in work time and major gains in productivity. It makes it easy to handle everything from design surveys and point-cloud scanning to AR, 3D construction, as-built management, and infrastructure inspection.

bottom of page